FHC210HDQ Brazed Plate Heat Exchanger

    • DETAIL
    Technical Parameters:     
    Heating Capacity
    150~450 KW Design pressure  3.0/4.5MPa 
    Max. Flow  105m3/h Test pressture   4.5/6.7MPa  
    Size
    732*322 mm Design temperature   -196℃~+200℃
    Plate Thickness
    0.4mm 
    Plate Channel
    H 
    Single Heat Exchanged Area
    0.210 ㎡
    Max. Thread connecting pipe size
    3" 
    Channel Volume
    0.40L/Channel Max. Solder connecting pipe size 3"1/8 
    Max. number of plates
    250
    Brazed
    copper brazed

    Model Number of plates Designed pressure>3.0 Designed pressure≤3.0 Weight(Kg) Volume(L) Surface area(㎡)
    A(mm) A(mm) F1F2Side F3F6=F4F5Side
    FHC210HDQ n 17+2.85n 13+2.85n 13+0.82n 0.40*1/2n 0.40*1/4(n-2) (n-2)0.210
    30 103 99 37.6 6.000 2.800 5.880
    50 160 156 54.0 10.000 4.800 10.080
    70 217 213 70.4 14.000 6.800 14.280
    90 274 270 86.8 18.000 8.800 18.480
    110 331 327 103.2 22.000 10.800 22.680
    130 388 384 119.6 26.000 12.800 26.880
    150 445 441 136.0 30.000 14.800 31.080
    170 502 498 152.4 34.000 16.800 35.280
    190 559 555 168.8 38.000 18.800 39.480
    210 616 612 185.2 42.000 20.800 43.680
    230 673 669 201.6 46.000 22.800 47.880
    250 730 726 218.0 50.000 24.800 52.080